China Orland battery D12-100/12v100Ah model and specification reference - China Supplier
China Orland battery D12-100/12v100Ah model and specification reference - China Supplier China Orland battery D12-100/12v100Ah model and specification reference - China Supplier China Orland battery D12-100/12v100Ah model and specification reference - China Supplier China Orland battery D12-100/12v100Ah model and specification reference - China Supplier China Orland battery D12-100/12v100Ah model and specification reference - China Supplier

Orland battery D12-100/12v100Ah model and specification reference

Electrical Equipment & Supplies/Batteries/Storage Batteries


Contact Info
  • Room 313, 3rd Floor, Building 1, Courtyard 4, Fze Road, Fangshan District, Beijing, 10000
  • 胡祥飞
  • 17662238989
  • zxc123321_0823@qq.com

Basic Information

  • Model: D12-100
  • Type: Valve-regulated sealed lead-acid maintenance-free battery
  • Rated Voltage: 12V
  • Rated Capacity: 100Ah (20-hour rate)

Product Features

  • Long Service Life Design: Adopts mature plate manufacturing technology and unique formula, the grid has good corrosion resistance, and the designed service life can reach more than 15 years under normal floating charge state (25℃ environment).
  • Stable Performance: The high-strength tight assembly process improves the assembly tightness of the battery, reduces the risk of active material shedding. At the same time, the battery has low internal resistance and excellent high-current discharge performance, which is more than 20% higher than similar products.
  • Low Self-discharge Rate: Selects high-spec lead alloy raw materials. After standing for 28 days at 25℃ room temperature, the self-discharge rate is less than 3%, which is better than the industry standard. No need to recharge after storing at room temperature for more than half a year.
  • Excellent Consistency: Automated production process combined with online monitoring equipment ensures the consistency of plates and batteries, making it suitable for series-parallel application scenarios of whole packs.
  • Safe and Reliable: Adopts combined maze post sealing technology, no leakage and no acid creep throughout the entire life cycle. The internal configuration of a special safety valve can effectively isolate external sparks.
  • Easy to Use: The special oxygen absorption cycle design solves the problem of electrolytic water loss during charging, and no electrolyte needs to be added during use. Supports multiple installation methods such as vertical, side lying and stacking, with high flexibility.

Performance Parameters

  • Charging Voltage: At 25℃ environment, the charging voltage is 14.1-14.7V, and the charging current shall not exceed 25% of the rated capacity (i.e. 25A).
  • Operating Temperature Range: Charging temperature 0℃-+40℃, discharging temperature -20℃-+55℃.

Application Fields

  • UPS Uninterruptible Power Supply: Provides backup power for equipment such as computers and servers, ensuring continuous operation of equipment and data security when the mains power is interrupted.
  • Communication System: Suitable for equipment such as communication base stations, maintaining the normal operation of communication equipment and ensuring network unblocked when power is interrupted.
  • Medical Equipment: Can provide emergency power support for medical monitoring equipment, first-aid equipment and other equipment, ensuring reliable operation in medical scenarios.
  • Emergency Lighting System: Used for emergency lighting in buildings and public places, providing lighting during power outages or emergencies to ensure the safety of personnel evacuation.
  • Security System: Powers monitoring cameras, alarm devices and other equipment to ensure the all-weather stable operation of security equipment.

Usage Precautions

  • Charging Requirements: New batteries do not need pre-charging before use, and can be charged after being put into use. The first three charging times shall not be less than 10 hours. It is recommended to use automatic current-limiting constant voltage charging equipment.
  • Installation Environment: The battery should be installed in a clean, cool, ventilated and dry place, avoid direct sunlight and heat radiation, and the battery spacing should be more than 20mm. If conditions permit, installing it in an environment with a constant temperature of about 20℃ can prolong the service life.
  • Maintenance Points: Avoid overcharging, over-discharging and deep discharging. Regularly detect the floating charge voltage and internal resistance of the battery, and replace the batteries with degraded performance in time. Charge in time after each discharge, and avoid long-term storage or long-term floating charge without discharging.