China Surge Protective Device (Lightning Arrester) - China Supplier

Surge Protective Device (Lightning Arrester)

Price:1
Industry Category: Electrical-Equipment-Supplies
Product Category:
Brand: 各大品牌
Spec: 一类 二类 三类


Contact Info
  • Add:山西省太原市小店区平阳南路晋阳街口君怡小区D座3单元1001, Zip: 030000
  • Contact: 李小鹏
  • Tel:03518066715
  • Email:2362324763@qq.com

Other Products

Description
Additional Information

Name: Module SPD Surge Protective Device

Model: 380V Three-phase Five-wire TC40-385/4, TC40-385/3+NPE; 220V Single-phase TC40-385/2, TC40-385/1+NPE

Brand: TOP

Color: Red

The TC40 series is a Class C (designed according to Class II test requirements) switching surge protective device, suitable for secondary protection of load equipment in building, automation, and computer room power distribution lines, preventing low-voltage equipment from overvoltage interference. It is installed at the LPZ0B-1 or higher interface.

Performance Features:

- Modular structure for easy operation and maintenance

- Visual failure indicator window

- Equipped with remote signaling contacts for remote monitoring

- Strong current-carrying capacity, fast response time, low residual voltage

- Multi-functional connection ports for wires and busbars

- Dual thermal trip device for reliable protection


Product Installation:

1. The SPD is used for secondary lightning protection in 220V/380V main distribution systems. It is installed in parallel at the power inlet of building distribution boxes or computer rooms, mounted on a 35mm electrical rail. Kelvin connection can be adopted. Before installation, the power must be turned off; live operation is strictly prohibited.

2. During installation, connect according to the installation diagram: L for phase line, N for neutral line, PE for ground line. Do not misconnect. After installation, close the circuit breaker switch and check if the working status is normal.

3. During use, regularly inspect the lightning protection module and check the status of the fault display window. If the fault display window turns red or the remote signaling terminal outputs an alarm signal, it indicates a fault in the lightning protection module, and it should be repaired or replaced promptly.

4. Suitable for indoor operation. If installed outdoors, a waterproof enclosure must be added.

5. All wiring must be secure and ensure reliable electrical connections. SPD connection wire: BVR ≥ 10mm²; ground wire: BVR ≥ 16mm². The lead length should be less than 0.5m and as short as possible.

6. Lightning protection grounding should comply with lightning protection standards. The ground wire should be as thick and short as possible, with a short grounding path for equipotential connection via grounding conductors.
Technical Parameters:

Model

TC40-385/2

TC40-385/1+N

TC40-385/4

TC40-385/3+N

Nominal Operating Voltage Un

220V/50Hz

380V/50Hz

Continuous Operating Voltage [L-N] Uc

385V

Continuous Operating Voltage [N-PE] Uc

255V

Nominal Discharge Current (8/20μS) In

20kA

Discharge Current (8/20μS) [N-PE] Iimp

40kA

Lightning Impulse Current (8/20μS) Imax

12kA

Voltage Protection Level (In) [L-N] Up

≤1.75kV

Voltage Protection Level (In) [N-PE] Up

≤1.25kV

Response Time [L-N] tA

≤25ns

Response Time [N-PE] tA

≤100ns

Backup Fuse

125A gl/gG

Short-Circuit Capacity

25kA/50Hz

Temperature Range

-40℃…+80℃

Installation Wiring Method/Specification

Parallel/Stranded 16mm²

Operating Indicator

Green/Red

Housing Material

Red Reinforced Thermoplastic, UL94-V0

Installation Width

2 Standard Modules

4 Standard Modules

Mounting Bracket

35mm Electrical Rail

Protection Level

IP20

TC20-… FM Additional Parameters

Remote Alarm Terminal Type

Switch Changeover Contact

Remote Signal

AC: 250V/0.5A

Remote Signaling Terminal Wiring Specification

1.5mm²

Industry Category Electrical-Equipment-Supplies
Product Category
Brand: 各大品牌
Spec: 一类 二类 三类
Stock:
Origin: China / Shanxi / Taiyuanshi
About Toocle.com - Partner Programme - Old Version
Copyright © Toocle.com. All Rights Reserved.
(浙)-经营性-2023-0192