SUNUSA High-Frequency Series UPS SA1101L
Contact Info
- Add:吉林省吉林市船营区光华路6号物华商城电城3048房间, Zip: 130000
- Contact: 牟继承
- Tel:13704310205
- Email:995075736@qq.com
Other Products
SA1101L
Technical Parameters:
Model: SA1101L
Phase: Single-phase grounding
Capacity: 1000VA/900W
Input Voltage Range: 110-300VAC at 50% load, 160-280VAC at 100% load
Input Frequency Range: 40Hz~70Hz
Input Power Factor: ≥0.99 at 100% load
Output Voltage: 200/208/220/230/240VAC
Output Voltage Range (Battery Mode): ±1%
Output Frequency Range (Synchronization Correction Range): 47~53Hz or 57~63Hz
Output Frequency Range (Battery Mode): 50Hz±0.25Hz or 60Hz±0.3Hz
Output Surge Ratio: 3:1
Output Harmonic Distortion: ≤3% THD (linear load), ≤6% THD (non-linear load)
Conversion Time AC to DC: 0ms
Conversion Time Inverter to Bypass: 4 ms (under standard conditions)
Waveform (Battery Mode): Pure sine wave
Mains Mode Efficiency: 88%
Battery Mode Efficiency: 83%
Standard Battery Model: 12V/7AH(B)
Number of Standard Batteries: 2
Maximum Charging Current for Standard Batteries: 1.0A (max)
Charging Voltage for Standard Batteries: 27.4VDC±1%
Extended-Run Battery Model: Depends on the applicant
Number of Extended-Run Batteries: 3 (specific 2)
Maximum Charging Current for Extended-Run Batteries: 1A/2A/4A/6A (adjustable)
Charging Voltage for Extended-Run Batteries: 41.0VDC±1% or 27.4VDC±1% (specific)
LCD or LED Display: Load level, battery capacity, mains mode, battery mode, bypass mode, fault indication;
Note: Standard LED display for domestic, LCD display for international
Battery Mode Alarm: Beeps once every 4 seconds
Low Battery Alarm: Beeps once every 1 second
Overload Alarm: Beeps once every 1 second
Fault Alarm: Continuous beeping
Standard Unit Dimensions, Depth×Width×Height (mm): 282×145×220
Standard Unit Net Weight (kg): 9.8
| Industry Category | Electrical-Equipment-Supplies |
|---|---|
| Product Category | |
| Brand: | SUNUSA |
| Spec: | |
| Stock: | 1000 |
| Manufacturer: | |
| Origin: | China / Jilin / Jilinshi |