A gas alarm is a flameproof safety device capable of rapidly, reliably, stably and continuously detecting gas concentration in industrial production. When the detected gas concentration reaches the preset alarm value of the gas alarm, the alarm will trigger an alert and drive external devices to remind on-site staff to take necessary protective measures, preventing gas-induced combustion accidents.
Working Principle of Gas Alarm: The alarm installed on-site operates with power supply. When a gas leak occurs, the sensor converts the detected leakage amount into a corresponding voltage signal. After the voltage signal is processed by the alarm, the data is uploaded and displayed on the screen. When the concentration reaches the set action value, the alarm triggers an alert and drives external devices.
A gas alarm is a fixed instrument that can continuously detect the concentration of oxygen, toxic and harmful gases, or flammable and explosive gases in the working environment.
The gas alarm adopts a diffusion method to convert the gas concentration signal at the monitoring point into an electrical signal in real time. After the signal is amplified, it is processed by the CPU through AD sampling, temperature compensation and intelligent calculation. If the measured value exceeds the set alarm concentration value, an alarm signal will be issued.
The gas alarm features a dual-chamber design, special imported sensors, and the sensors adopt a modular design, making calibration and adjustment more convenient. It has superior performance, high stability, can output multiple sets of signals, and is easy to install and maintain, meeting the high reliability requirements of industrial on-site equipment.
Features
Ingenious structural design, extremely easy to install;
Upper and lower limit alarm points can be set arbitrarily within the full range;
Flameproof design, suitable for hazardous locations in Division 1 and Division 2 of factory conditions;
The gas alarm can be optionally equipped with a liquid crystal concentration display, showing the concentration in real time on site;
The gas alarm can be optionally equipped with a special flameproof acoustic-optic alarm to realize on-site acoustic-optic alarm;
Meets customer's requirements for any range from 1 to 99999 and all gas detection needs;
Two sets of normally open passive contact outputs, used for controlling AC contactors of fans or solenoid valves;
Exquisite power supply design, with pure SMT component patch process, ensuring stable product performance;
The sensor uses imported gas-sensitive components, with high precision, long service life, small zero drift, fast response time, long-term continuous operation, small body size, convenient operation, and good anti-poisoning performance;
The alarm point adjustment, zero adjustment and target point calibration of the transmitter can be performed through the controller without opening the cover;
Suitable for dozens of gas detections and can display gas names; Gas unit names: ppm, LEL%, VOL%, mg/m³;
The international standard (4~20)mA signal can be directly connected to the factory DCS system, and the RS485 digital signal is connected to the factory host computer
Accuracy | ±2%FS (high-precision type), ±5%FS (general type) |
Weight | 1.5Kg |
Warranty Period | 12 months |
Output Signal | 4-20mA/RS485/Passive Switch Quantity |
Interlocking Equipment | Fan, Solenoid Valve, Fire Protection System, etc. (24VDC/1A) |
Flameproof Type | Intrinsically Safe Type |
Flameproof Mark | Ex d II C T6 Gb |
Working Voltage | DC12-24V±1% |
Dimension Specification | 140mm (length) * 164mm (width) * 75mm (height) |
Housing Material | Stainless Steel / Aluminum Alloy |
Sampling Method | Diffusion Type or Pipeline Type |
Temperature Grade | -40℃~+65℃ (Standard Type) / -40℃~+70℃ (Extreme Type) |
Humidity Grade | 15~95% RH (No Condensation) |
Ambient Pressure | 86kPa ~106kPa |
Service Life | More than 3 years |
| Industry Category | Instruments & Meters/Other Instruments/Gas Alarms & Detectors |
|---|---|
| Product Category | |
| Brand: | 贝斯安 |
| Spec: | BSA/QT-BJ |
| Origin: | 114403 |