China ND5800 Dual-Clamp Multifunctional Ground Resistance Tester - China Supplier
China ND5800 Dual-Clamp Multifunctional Ground Resistance Tester - China Supplier

ND5800 Dual-Clamp Multifunctional Ground Resistance Tester

Price:元订货量(PCS) ≥1
Industry Category: Measurement-Analysis-Instruments
Product Category:
Brand: 武汉诺顿whnort
Spec: ND5800


Contact Info
  • Add:武汉市东湖开发区高新四路40号, Zip: 430074
  • Contact: 蔡先生
  • Tel:+8613871491300
  • Email:whnort@163.com

Other Products

Description
Additional Information

Product Introduction

   ND5800 Dual-Clamp Multifunctional Ground Resistance Tester is a commonly used instrument for inspecting and measuring ground resistance. It features an extra-large LCD gray-white backlit display and microprocessor technology, enabling ground resistance testing via 2-wire, 3-wire, and 4-wire methods, as well as soil resistivity testing, all controlled by the microprocessor. It integrates numerous grounding test functions, allowing for quick and comprehensive measurement of various parameters in grounding networks. Widely used in telecommunications, power, meteorology, computer rooms, oil fields, power distribution lines, transmission line towers, gas stations, factory grounding networks, lightning rods, etc. The instrument is characterized by accuracy, speed, simplicity, stability, and reliability.

   ND5800 Dual-Clamp Multifunctional Ground Resistance Tester consists of a host unit, monitoring software, test leads, USB cable, and grounding stakes. It offers functions such as historical data reading, reviewing, saving, reporting, and printing.


Product Features

   ND5800 Dual-Clamp Multifunctional Ground Resistance Tester is microprocessor-controlled, providing precise detection of ground resistance, soil resistivity, and ground voltage. It utilizes fast filtering technology to minimize interference. The resistance values of auxiliary electrodes are displayed on the same screen, facilitating the identification of measurement errors caused by environmental factors and enabling more accurate measurement of true ground resistance. It can store 500 sets of data, supports online data monitoring via software, USB data upload to PC, and features unique functions such as data hold and intelligent protection alerts.

  

Technical Parameters

1. Range and Accuracy Error

Measurement Function

Measurement Range

Accuracy

Resolution

2/3/4-Wire Ground Resistance (Re)

0.00Ω~29.99Ω

±2%rdg±5dgt(Note 1)

0.01Ω

30.0Ω~299.9Ω

±2%rdg±3dgt

0.1Ω

300Ω~2999Ω

±2%rdg±3dgt

3.00kΩ~30.00kΩ

±2%rdg±3dgt

10Ω

DC Resistance (R—)

0.0Ω~299.9Ω

±2%rdg±3dgt

0.1Ω

300Ω~2999Ω

±2%rdg±3dgt

3.00kΩ~30.00kΩ

±2%rdg±3dgt

10Ω

Selective Ground Resistance (Re)

0.00Ω~29.99Ω

±2%rdg±5dgt(Note 1)

0.01Ω

30.0Ω~299.9Ω

±2%rdg±3dgt

0.1Ω

300Ω~3000Ω

±2%rdg±3dgt

Dual-Clamp Ground Resistance (Re)

0.01Ω~0.99Ω

±10%rdg±10dgt

0.01Ω

1.0Ω~9.9Ω

0.1Ω

10Ω~100Ω

Soil Resistivity (ρ)

0.00Ωm~99.99Ωm

ρ=2πaR (Note 2)

0.01Ωm

100.0Ωm~999.9Ωm

0.1Ωm

1000Ωm~9999Ωm

1Ωm

10.00kΩm~99.99kΩm

10Ωm

100.0kΩm~999.9kΩm

100Ωm

1000kΩm~9999kΩm

1kΩm

Ground Voltage

AC 0.00~100.0V

±2%rdg±3dgt

0.01V

AC Current

AC 0.0mA~1000A

±2%rdg±3dgt

0.1mA

Operating Conditions: Rh max=3kΩ+100R<50kΩ;Rs max=3kΩ+100R<50kΩ

Note: 1. Reference condition: Accuracy when Rh Rs<100Ω.

  2. Depends on the measurement accuracy of R, π=3.14, a:1 m~100m;

2. General Specifications

Function

Ground resistance, soil resistivity, DC resistance, ground voltage, AC current,

Ambient Temperature & Humidity

23℃±5℃,below 75%rh

Interference Voltage

<20V (should be avoided)

Interference Current

<2A (should be avoided)

Electrode Spacing for R Measurement

a>5d

Electrode Spacing for ρ Measurement

a>20h

Power Supply

DC 6V 4.5Ah Lead-Acid Battery, continuous standby over 100 hours

Backlight

Controllable backlight, suitable for dimly lit environments

Measurement Methods

Precision 4-wire, 3-wire method, simple 2-wire, selective method, dual-clamp method for ground resistance measurement

Measurement Techniques

2/3/4-wire method: Pole-changing method, max test current 20mA

Soil resistivity: 4-pole method

Selective method: Pole-changing method, max test current 20mA

Dual-clamp method: Non-contact mutual inductance method, max test current 1mA

DC resistance: Pole-changing method

AC current: Average rectification (clamp type)

Ground voltage: Average rectification (between S-ES interface)

Test Voltage Waveform

Sine wave

Test Frequency

128Hz

Short-Circuit Test Current

AC 20mA max

Open-Circuit Test Voltage

AC 28V max

Electrode Spacing Range

1m~100m

Display Mode

4-digit extra-large LCD with backlight

Measurement Indicator

LED blinking during measurement

LCD Size

111mm×68mm

LCD Display Area

108mm×65mm

Instrument Dimensions

L×W×H: 277.2mm×227.5mm×153mm

Clamp Dimensions

L×Thickness×H: 101mm×27mm×214mm

Test Leads

4 wires: red 15m, black 15m, yellow 10m, green 10m each

Simple Test Leads

2 wires: yellow 1.5m, green 1.5m each

Auxiliary Grounding Rods

4 rods: φ10mm×200mm

Current Clamps

2 clamps: banana plugs

Clamp Jaw Diameter

φ50mm

Current Clamp Leads

Industry Category Measurement-Analysis-Instruments
Product Category
Brand: 武汉诺顿whnort
Spec: ND5800
Stock: 100
Manufacturer:
Origin: China / Hubei / Wuhanshi
About Toocle.com - Partner Programme - Old Version
Copyright © Toocle.com. All Rights Reserved.
(浙)-经营性-2023-0192