New air low-temperature cold air unit for temperatures from -5℃ to -40℃ (24/7 operation)
Contact Info
- Add:深圳市龙岗区坪地街道年丰社区横岭中路1号第七栋, Zip: 518116
- Contact: 李大红先生
- Tel:0755-29084657
- Email:szkawai@yeah.net
Other Products
Low-Temperature Cold Air Units for Scientific Research
Low-temperature cold air units for scientific research are air-cooled refrigeration equipment that provides a cold source ranging from -5°C to -40°C for research experiments. At specific temperatures, researchers can read the physical data of experiments. The temperature range of the low-temperature cold air units introduced by our company: the new natural air can reach as low as -40°C, operating continuously 24 hours a day; the cold air can reach as low as -90°C, operating continuously 24 hours a day.
Working Principle
According to the principle of the refrigeration system: low-temperature, low-pressure liquid refrigerant undergoes heat exchange with the air flowing into the evaporator. The evaporator absorbs heat from the air. During the evaporation process, the temperature of the refrigerant remains unchanged. The liquid refrigerant evaporates into a low-temperature, low-pressure gaseous refrigerant and enters the compressor. After being compressed by the compressor, it becomes a high-temperature, high-pressure gaseous refrigerant and then enters the condenser. In the condenser, it undergoes heat exchange with the natural air drawn by the cooling fan, discharging the heat of the high-temperature, high-pressure refrigerant out of the unit. The refrigerant flows out of the condenser and passes through a dryer filter to remove moisture or other impurities contained in the refrigerant during the evaporation process. It then enters the expansion valve for expansion and throttling, which is a rapid cooling process. The refrigerant becomes a low-temperature, low-pressure liquid. After this process, the refrigerant re-enters the evaporator for heat exchange and evaporation, thereby completing the entire refrigeration system process. This cycle continues continuously, allowing the water to achieve continuous refrigeration. The cold air is then delivered to the desired cooling destination through the fan via the air outlet.
Unit Selection
Low-temperature cold air units for scientific research are available in split and integrated designs. The split type is suitable for space cooling, with an installation method similar to that of household air conditioners: the condenser is installed outdoors, while the main unit is installed indoors. The integrated unit is more widely applicable, with the main unit for space cooling placed outdoors and connected to air ducts leading indoors. Note: This is fresh air and can also be configured as recirculated air.
Unit Features:
1.PLC control system.
2. Touch screen human-machine interface.
3. R485 communication port can connect to the upper computer to read and print experimental data.
4. Temperature control: new natural air -40 to 50°C ±2; cold air -90 to 0°C ±0.5.
After-Sales Service
All equipment from our company comes with a one-year warranty and lifelong maintenance (excluding human factors and consumable parts).
Upon receiving a written equipment repair notice from the customer, we will respond and arrive for repairs within 36 hours for locations within Guangdong Province and within 72 hours for locations outside Guangdong Province.
Unit Technical Parameters
Model | Refrigeration Capacity | Compressor | Evaporator | Condenser | Fan | Air Outlet Air outlet | Dimensions Shape dimension | Net Weight Net weight | ||
kcal/h | kw | kw | hp | m3/h | m3/h | kw | mm | cm | kg | |
JRA-05AL | 12470 | 14.5 | 3.75 | 5 | 1000 | 5000 | 0.75 | 125 | 120×60×143 | 160 |
JRA-06AL | 14964 | 17.4 | 4.5 | 6 | 1200 | 6000 | 1.1 | 125 | 126×65×155 | 220 |
JRA-08AL | 19552 | 23.2 | 3×2 | 8 | 1600 | 8000 | 1.1 | 150 | 130×65×160 | 240 |
JRA-10AL | <极>29 | 7.5 | 10 | 2000 | 10000 | 1.5 | 150 | 148×70×168 | 310 | |
JRA-12AL | 29928 | 34.8 | 4.5×2 | 12 | 2400 | 12000 | 1.5 | 180 | 150×70×173 | 430 |
JRA-15AL | 37410 | 43.5 | 5.5×2 极> | 15 | 3000 | 15000 | 2.2 | 180 | 160×75×190 | 480 |
JRA-20AL | 49880 | 58 | 7.5×2 | 20 | 4000 | 20000 | 3 | 200 | 170×90×210 | 660 |
JRA-25AL | 59856 | 69.6 | 9×2 | 25 | 5000 | 25000 | 3.75 | 200 | 190×100×210 | 740 |
JRA-30AL | 74820 | 87 | 7.5×3 | 30 | 6000 | 30000 | <极> 4 | 200 | 220×100×210 | 810 |
JRA-40AL | 99760 | 116 | 7.5×4 | 40 | 8000 | 40000 | 5.5 | 200 | 240×140×220 | 980 |
JRA-50AL | 124700 | 145 | 7.5×5 | 50 | 10000 | 50000 | 7.5 | 200 | 250×150×220 | 1200 |
| Industry Category | Machinery & Industrial Equipment |
|---|---|
| Product Category | |
| Brand: | Ninewells |
| Spec: | JRA-10AL |
| Stock: | 0 |
| Origin: | China / Guangdong / Shenshi |