Tunnel Cooling Freezing Air Conditioning Unit (Tunnel Cooling Air Conditioner)
Contact Info
- Add:深圳市龙岗区坪地街道年丰社区横岭中路1号第七栋, Zip: 518116
- Contact: 李大红先生
- Tel:0755-29084657
- Email:szkawai@yeah.net
Other Products
Engineering Tunnel Cooling Freezing Air Unit
During tunnel excavation, high-temperature surrounding rock may expose workers and equipment to extreme heat, adversely affecting health and work efficiency. Traditional tunnel cooling methods rely on ventilation, which draws fresh air from the tunnel entrance and delivers it near the excavation face. However, in long tunnels, the air heats up due to prolonged exposure to high temperatures from the surrounding rock, reaching nearly the same temperature as the tunnel environment before it arrives at the work area, rendering the cooling effect minimal. Efficiently and economically reducing high temperatures in deep, long tunnels during construction to improve the working environment is an urgent issue. Therefore, a movable, custom-designed freezing air unit must be installed in the tunnel to provide localized cooling in the work area, lowering the temperature and creating a cooler environment for construction personnel.
Unit Advantages
1.
3. Rapid cooling, high air volume, ventilation, dehumidification, dust prevention, and heatstroke prevention advantages. Improves mining efficiency, saves electricity, reduces costs, quick installation, and easy maintenance.
4. Integrated unit design for easy mobility.
5. All components are original, brand-new products from the factory, using stable and reliable brands with low failure rates. Our company strictly prohibits the use of refurbished compressors.
Working Principle
Select a location in the tunnel to place the cooling freezing air unit. It extracts air from the tunnel, cools it, and uses it as a cold source. The fan then delivers this cold air to the mining work area for effective cooling, reducing the temperature to the desired level.
Tunnel Cooling Freezing Air Unit Features.
1. Scientifically designed, meticulously manufactured, aesthetically pleasing appearance, reliable performance, and high quality.
2. Equipped with centrifugal fans for high air volume, long-distance air delivery, and low noise.
3. The unit includes eight protection functions: high-pressure protection, low-pressure protection, phase sequence protection, phase loss protection, overheating protection, overload protection, freeze protection, and air shortage protection.
4. The unit control uses a human-machine interface microcomputer system, which can include a touch screen and features an R485 communication port for remote control.
6. Uses national standard refrigerants. Our company independently develops mixed refrigerants that can be selected based on different usage environments.
Our Services
1.
2.
3.
Unit Technical Parameters
Model | Refrigeration Capacity | Compressor | Evaporator | Condenser | Fan | Air Outlet Air outlet | Dimensions Shape dimension | Net Weight Net weight | ||
kcal/h | kw | kw | hp | m3/h | m3/h | kw | mm | cm | kg | |
JRA-20A | 49880 | 58 | 15 | 20 | 4000 | 20000 | 3 | 200 | 170×90×210 | 660 |
JRA-25A | 59856 | 67 | 18 | 25 | 5000 | 25000 | 3.75 | 200 | 190×100×210 | 740 |
JRA-30A | 74820 | 87 | 22 | 30 | 6000 | 30000 | 4 | 200 | 220×100×210 | 810 |
JRA-40A | 99760 | 116 | 28 | 40 | 8000 | 40000 | 5.5 | 200 | 240×140×220 | 980 |
JRA-50A | 124700 | 145 | 37 | 50 | 10000 | 50000 | 7.5 | 200 | 250×150×220 | 1200 |
JRA-60A | 149640 | 174 | 45 | 60 | 12000 | 60000 | 11 | 200 | 270×170×240 | 1400 |
2. Condenser inlet water temperature 30°C, condenser outlet water temperature 35°C. Cooling water temperature into 30°C, Cooling water temperature for 35°C.
2. The above parameters are subject to change without prior notice. The above parameters are subject to change without prior notice.
| Industry Category | Machinery & Industrial Equipment |
|---|---|
| Product Category | |
| Brand: | Ninewells |
| Spec: | JRW-60A |
| Stock: | 0 |
| Origin: | China / Guangdong / Shenshi |