KCD2-UT2-Ex1 Temperature Transmitter Safety Barrier
Contact Info
- Add:, Zip:
- Contact: 陈小姐
- Tel:18221776086
- Email:2501529964@qq.com
Other Products
KCD2-UT2-Ex1 Temperature Transmitter Barrier Features
• Single-channel barrier
• 24V DC power supply (rail-powered)
• Thermocouple, RTD, potentiometer, or voltage input
• Current output 0/4 mA ... 20 mA
• Passive or active output
• Configurable via PACTware™ software
• Line fault (LFD) and sensor detection
KCD2-UT2-Ex1 Temperature Transmitter Barrier is suitable for intrinsically safe applications. This device converts RTD or thermocouple input signals from hazardous areas into 0/4 mA ... 20 mA signals in safe areas. When internal cold junction compensation is required, the detachable terminal block KC-CJC-** for thermocouples can be selected. Faults are indicated via LED indicators compliant with NAMUR NE44 and user-configurable fault output signals.
When used with power rail products, this device supports error signal acquisition. It can be conveniently configured using PACTware™ configuration software.
Technical Data
Power Supply
Rated voltage 19 ... 30 V DC
Power dissipation / power consumption ≤ 0.98 W / 0.98 W
Input
RTD
Types Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995)
Types Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94)
Types Cu10, Cu50, Cu100 (P50353-92) Type Ni100 (DIN 43760)
Measuring current approx. 200μA, RTD
Wiring types 2-wire, 3-wire, 4-wire
Lead resistance per wire ≤ 50 Ω
Thermocouple
Types B, E, J, K, N, R, S, T (IEC 584-1: 1995)
Type L (DIN 43710: 1985)
Types TXK, TXKH, TXA (P8.585-2001)
Cold junction compensation External and internal
Potentiometer 0 ... 20kΩ (2-wire)
0.8 ... 20kΩ (3-wire)
Voltage Selectable range -100 ... 100 mV
Input resistance ≥ 1 MΩ (-100 ... 100 mV)
Output
Output Analog current output
Current range 0 ... 20 mA or 4 ... 20 mA
| Industry Category | Measurement-Analysis-Instruments |
|---|---|
| Product Category | |
| Brand: | 倍加福 |
| Spec: | KCD2-UT2-Ex1 |
| Stock: | 100 |
| Manufacturer: | |
| Origin: |