KCD2-UT2-Ex1 Temperature Transmitter Barrier Features

• Single-channel barrier

• 24V DC power supply (rail-powered)

• Thermocouple, RTD, potentiometer, or voltage input

• Current output 0/4 mA ... 20 mA

• Passive or active output

• Configurable via PACTware™ software

• Line fault (LFD) and sensor detection


KCD2-UT2-Ex1 Temperature Transmitter Barrier is suitable for intrinsically safe applications. This device converts RTD or thermocouple input signals from hazardous areas into 0/4 mA ... 20 mA signals in safe areas. When internal cold junction compensation is required, the detachable terminal block KC-CJC-** for thermocouples can be selected. Faults are indicated via LED indicators compliant with NAMUR NE44 and user-configurable fault output signals.

When used with power rail products, this device supports error signal acquisition. It can be conveniently configured using PACTware™ configuration software.


Technical Data

Power Supply

Rated voltage 19 ... 30 V DC

Power dissipation / power consumption ≤ 0.98 W / 0.98 W

Input

RTD

Types Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995)

Types Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94)

Types Cu10, Cu50, Cu100 (P50353-92) Type Ni100 (DIN 43760)

Measuring current approx. 200μA, RTD

Wiring types 2-wire, 3-wire, 4-wire

Lead resistance per wire ≤ 50 Ω

Thermocouple

Types B, E, J, K, N, R, S, T (IEC 584-1: 1995)

Type L (DIN 43710: 1985)

Types TXK, TXKH, TXA (P8.585-2001)

Cold junction compensation External and internal

Potentiometer 0 ... 20kΩ (2-wire)

0.8 ... 20kΩ (3-wire)

Voltage Selectable range -100 ... 100 mV

Input resistance ≥ 1 MΩ (-100 ... 100 mV)

Output

Output Analog current output

Current range 0 ... 20 mA or 4 ... 20 mA