Brass Static Balancing Valve

Function and Application

The BSSVP static balancing valve is suitable for air conditioning, heating, and process water systems to achieve static hydraulic balance. It also enables system fault diagnosis through the measurement function of the static balancing valve.

Working Principle

The BSSVP static balancing valve is installed at various locations in the water system. By manually adjusting the valve opening, it changes the resistance distribution of the pipeline network, regulates the static hydraulic balance between branches or terminals of the circulating water system, and ensures that different branches or terminals achieve the designed flow rate.

Product Features

1.Precise Flow Control:

2.Digital Handwheel Opening Indicator:

3.Simple Opening Locking:

4.Shut-off Function via Handwheel:

5.Self-sealing Pressure Measurement Port.

Technical Parameters

Nominal Diameter

DN15-DN50

Pressure Rating

PN16/PN25

Operating Temperature

-10~120℃

Working Medium

Air Conditioning Chilled/Hot Water, Glycol Solution

Connection Standard

G Thread according to GB/T7

Design Standard

GB/T28636-2012

Parts Material

1

Valve Body

Brass

2

Valve Core

Copper Alloy

3

Valve Seat Seal

PTFE

4

Valve Cover

Brass

5

Stem

Copper Alloy

6

Locking Pin

Copper Alloy

7

Handwheel

Polyamide Plastic

8

Stem Seal

EPDM O-Ring

9

Measurement Nozzle

Brass

Dimensions

Diameter

L (mm)

H (mm)

D

DN15

80

114

G1/2

DN20

84

116

G3/4

DN25

98

119

G1

DN32

110

136

G1-1/4

DN40

120

138

G1/2

DN50

150

148

G2

Valve Kv Value

Turns

DN15

DN20

DN25

DN32

DN40

DN50

0.5

0.86

0.90

1.51

1.92

2.49

3.58

1.0

1.50

1.55

2.28

3.44

4.43

6.28

1.5

2.08

2.14

3.02

5.42

7.08

9.36

2.0

2.27

2.66

3.67

7.28

9.41

12.29

2.5

2.64

3.43

4.47

9.28

12.30

15.89

3.0

2.92

3.96

5.72

12.20

16.36

21.59

3.5

3.31

4.53

7.04

15.11

19.90

28.00

4.0

3.61

4.96

7.87

17.25

23.98

33.61

4.5

3.88

5.71

8.89

19.45

27.51

38.78


Installation and Usage Instructions

The static balancing valve is generally installed on the return pipe of the system. When used in conjunction with a dynamic differential pressure balancing valve, it is installed on the supply pipe. Typically, when connecting the static balancing valve to an elbow or a water pump, a certain straight pipe installation distance must be maintained. When connecting to an elbow, follow the principle of 5d before the valve and 2d after the valve. When connecting to a water pump, follow the 10d principle.