Lightning Protection Device MC50-B VDE
Contact Info
- Add:深圳市龙华区大浪街道龙华社区龙军花园9栋2单元1202, Zip: 518023
- Contact: 刘先生
- Tel:0755-88834928
- Email:1002196429@qq.com
Other Products
| Sealed structure design, no arc leakage during operation | Can be enclosed and installed in any standard distribution box |
| Passed safety tests, certified with VDE, OVE, KEMA, KEUR, MEEI, EZU test marks | Suitable for reliable protection in all applications, tested by multiple independent testing institutions. |
| Low protection level | Decoupler installation is only required when the distance (cable length) between Class B and Class C protectors is less than 5 meters. |
| Modular design | Facilitates easy inspection and maintenance |
| Two connection terminals provided at each end | Easy connection using Kelvin wiring method |
| High follow-current interruption capability | Can be used on lines close to transformers |
| Tunnel-type connection method provided | No grounding jumper required, installation is more convenient and safer |
Function and Application Areas
The Lightning Surge Protector MC 50-B VDE is a pluggable multi-layer spark gap device. The unit consists of 9 layers of spark gaps, which are formed by stacking 10 high-energy graphite electrode discs together. High-heat-resistant Teflon spacer rings reliably ensure the internal safety distance of the spark gaps. Bolt-fixed die-cast zinc metal connection plates combine the spark gaps and clamp them in precise positions. Eight of the nine spark gap layers are controlled by high-capacity capacitors, ensuring an accurately set protection level voltage of ≤2 kV.
Due to its unique sealed design structure, the Lightning Surge Protector MC50-B VDE produces no arc leakage even during operation. Therefore, no additional space for arc leakage needs to be reserved during installation.
This surge protector fully meets the requirements for Class B devices according to standard DIN VDE 0675 Part 6 (Draft 11.89) A1, A2, as well as the requirements for Class I surge protectors according to standard IEC 61643-1 (02.98). The device is designed for use between Zone 0 and Zone 1 (based on the lightning protection zone definitions in IEC 61312-1).
For lightning protection installation projects in buildings, the Surge Protector MC 50-B VDE provides equipotential bonding for lightning protection on power lines. The protector has successfully passed tests according to lightning current parameters (based on ENV 61024-1 and IEC 61024-1).
When lightning strikes an overhead line, the Lightning Controller MC 50-B VDE provides sufficient protection, making it suitable for use in power supply systems where electricity is introduced into buildings via overhead lines.
Installation
The housing dimensions of the Lightning Surge Protector MC 50-B VDE meet the space-saving 17.5mm width module requirement, making the device easy to install. Simple installation is achieved by snapping onto a 35mm rail. The L, N, and PE terminals of the MC 50-B VDE provide two connection ports, facilitating Kelvin wiring.
Note: Because the spark gaps of this protector are encapsulated, no arc leakage occurs outside the housing during operation, so no additional space for arc leakage needs to be reserved during installation.
Technical Parameters
| Rated Voltage UN | 230 V/50-60 HZ |
| Maximum Continuous Operating Voltage UC | 255 V |
| Demand Level -According to DIN VDE 0675 Part 6 (Draft 11.89) A1,A2 -According to IEC 61643-1 | B Class I |
| Lightning Protection Zone | 0→1 |
| Insulation Resistance Rins | >100 MΩ |
| Voltage Protection Level Up | <2 kV |
| Response Time TA | <100 ns |
Surge Current Test (10/350)-Based on lightning current parameters per IEC 61312-1(02.95) | 50 kA 25 As 0.63 MJ/Ω |
| Protector's follow-current interruption capability at UC Maximum Asymmetric Short-Circuit Current Ip | 12.5 kArms 25 kA |
| Maximum Series Fuse (required only if not present in the grid) | 500 A gL/gG |
| Short-Circuit Withstand Capacity (with 500A gL fuse in series) Maximum Asymmetric Short-Circuit Current Ip | 17.6 kArms 25 kA |
| Temperature Range υ | -40℃ to +85℃ |
| Air Humidity | ≤95% |
| IP Rating | IP 20 |
| Conductor Cross-Sectional Area Solid/Stranded/Stranded Flexible Wire Tightening Torque (MA) at least 4Nm | 10-50/ 10-25/ 10-35mm2 AWG 8-2 |
| Installation | Snap onto 35mm2 rail (According to DIN EN 50022) |
| Industry Category | Electrical-Equipment-Supplies |
|---|---|
| Product Category | |
| Brand: | 德国obo |
| Spec: | MC50-B VDE |
| Stock: | |
| Origin: | China / Guangdong / Shenshi |