DXC-20 Water Pump Unit Controller Specific Functional Parameters
Other Products
Introduction to Building Equipment Monitoring System
A building equipment monitoring system is a system used to monitor and manage the operational status of various equipment and systems within a building. It typically consists of sensors, data acquisition devices, data processing units, monitoring terminals, and control systems. It enables real-time monitoring, data collection, analysis, and control of building equipment to ensure normal operation and safety.
Building Equipment Monitoring SystemProduct Model:
For more product information or pricing, please call our company.
Product quotation contact number: 15O-O29O-668O
Please contact Manager Zhang: 15202906680
We will wholeheartedly provide you with project drawing design optimization and configuration plan quotations!!!
DXC-10 Fan Unit Controller
DXC-10 Fan Unit ControllerFunction Introduction
1. Can detect the actual electrical power of the fan, with interlocked startup for fans and fire dampers. Energy-saving operation of fans is automatically controlled by the controller through intermittent operation, local exhaust, and CO concentration in the basement.
2. Smoke exhaust and ventilation fans are set with fire protection priority, automatically switching to high-speed operation when there is a fire alarm input, and stopping other ventilation and exhaust fans. Equipment room supply and exhaust fans.
3. Equipped with an LCD screen for real-time data and status display, debugging, and settings.
4. 1 USB port, 2 RS485 communication interfaces, capable of supplying power to external communication links, and supports network port communication.
5. 12 universal inputs, 4 digital outputs, 4 analog outputs.
6. Serial port supports BACnet M, Modbus-RTU, etc.
7. 35mm standard rail-mounted installation.
DXC-20 Water Pump Unit Controller
DXC-20 Water Pump Unit ControllerFunction Introduction
1. Can achieve system control and manual control functions for rainwater/sewage pumps.
2. Can collect signals from branch sensors and switch feedback signals, and execute corresponding control logic based on sensor signals.
3. Switch loop protection function.
4. Delay protection, scenario programming.
DXC-30 Air ConditioningUnit Controller
DXC-30 Air ConditioningUnit ControllerFunction Introduction
1) Integrates the secondary circuit of the air conditioning electrical control box.
2) Manual remote sample - automatic control: equipment self-test.
3) Provides protection for air conditioning startup timeout, overload, phase loss, imbalance, underload, leakage, blockage protection, and power recovery.
4) Provides fault location and cause for air conditioning units and electrical control boxes, facilitating quick equipment maintenance.
5) Real-time tracking and recording of air conditioning efficiency and energy consumption data.
DXC-50 Cold Source Unit Controller
DXC-50 Cold Source Unit Controller Function Introduction
1. Performs cluster control of cold/heat source equipment, chilled water pump groups, cooling water pump groups, and cooling tower groups.
2. Real-time tracking and recording of unit efficiency, equipped with an LCD screen for real-time data and status display, debugging, and settings.
3. 1 USB port, 2 RS485 communication interfaces, capable of supplying power to external communication links.
4. 16 universal inputs, 6 digital outputs, 4 analog outputs.
5. Serial port supports BACnet MS, Modbus-RTU, etc.
6. 35mm standard rail-mounted installation.
| Industry Category | Machinery |
|---|---|
| Product Category | |
| Brand: | 亚川 |
| Spec: | DXC-20 |
| Stock: | 88 |
| Manufacturer: | |
| Origin: | China / Shaanxi / Xianshi |