Fully Automatic Transformer Ratio Tester
Contact Info
- Add:扬州宝应柳堡工业集中区范柳路55号, Zip: 225800
- Contact: 费苏强
- Tel:86-0514-88557066
- Email:yzkedq@163.com
Other Products
KEBBY-D1 Fully Automatic Turns Ratio Tester
I. Product Overview
During the production process of power transformers, whether semi-finished or finished products, before newly installed transformers are put into operation, and in accordance with the preventive test regulations of the power department, turns ratio or voltage ratio testing of transformers is required. Traditional ratio bridges are cumbersome to operate, provide non-intuitive readings, require necessary conversions, and can only perform single-phase testing, resulting in low work efficiency.
The KEBBY-D1 Fully Automatic Turns Ratio Tester overcomes the shortcomings of traditional ratio bridge testing. It features a large color LCD screen with Chinese menu prompts, making operation simple and intuitive. It completes three-phase ratio testing in one go, offering fast testing speed, high accuracy, and comprehensive protection functions.
II. Safety Measures
1. Be sure to read this manual carefully before using the instrument;
2. The operator of the instrument should have knowledge of electrical equipment or instruments;
3. The instrument must be reliably grounded during use;
4. The power supply for this instrument is AC220V±10%, 50/60Hz±1Hz;
5. The instrument outputs high voltage; pay attention to safety and prevent electric shock;
6. This instrument can be used both indoors and outdoors but should avoid harsh environments such as rain, corrosive gases, excessive dust, high temperatures, direct sunlight, etc.;
7. The instrument should avoid severe vibration;
8. Maintenance, care, and adjustment of the instrument should be performed by专职测试人员 (dedicated testing personnel);
9. The yellow, green, red, and black test clips correspond to the transformer's A, B, C, and O phases respectively; do not reverse the high and low voltage side test leads;
10. For single-phase measurement, only use the yellow and black clips; do not use the wrong ones. Unused test clips should be left suspended.
III. Performance Features
1. Wide testing range, up to 0.9~10000;
2. Fast testing speed, completing three-phase tests in about 10 seconds;
3. Capable of testing CTs, PTs, CVTs, and Z-connected transformers;
4. Features blind testing for ratio, group, and polarity;
5. Multiple measurement methods, making fault judgment easier;
6. Non-volatile clock and date display, data storage for 480 groups, data is not lost upon power failure;
7. Large color LCD display, clear and easy-to-read data;
8. The instrument has high and low voltage reverse connection protection, transformer short-circuit and inter-turn short-circuit protection, and a fast, silent thermal printer;
9. Compact size and light weight.
IV. Technical Specifications
Display Digits | 5 digits | |||
Output Voltage | AC160V | AC10V | ||
Range | 0.9-10000 | Auxiliary Voltage | ||
Testing Error | 0.9-2000 | ± 0.2% | ||
>3000 | ± 0.5% | |||
Resolution | 0.0001 | |||
Power Supply | AC220V±10%, 50/60Hz±1Hz | |||
Test Data Storage | 480 groups | |||
Operating Temperature | -15℃~45℃ | |||
Relative Humidity | ≤80%, no condensation | |||
Main Unit Dimensions | 325mm (L) × 275mm (W) × 140mm (H) | |||
Main Unit Weight | 4.5Kg | |||
Total Instrument Weight | 8.8 Kg | |||
| Industry Category | Measurement-Analysis-Instruments |
|---|---|
| Product Category | |
| Brand: | 凯尔 |
| Spec: | KEBBY-D1 |
| Stock: | 500 |
| Manufacturer: | |
| Origin: | China / Jiangsu / Yangzhoushi |