FZW28-12F/630A Outdoor High-Voltage Vacuum Load Switch, 10KV "Watchdog" Pole-Mounted Vacuum Circuit Breaker
Contact Info
- Add:Xiangyang Industrial Zone, Liushi Town, Yueqing City, Zip:
- Contact: 李经理
- Tel:15167417505
- Email:864640886@qq.com
Other Products
The FZW28 sectionalizer is an outdoor vacuum load switch specially designed for 10kV distribution systems. It is mainly installed at the demarcation point between overhead lines and users, used for automatic fault isolation and location, and improving the power supply reliability of the power grid.
Main Features and Functions
Applicable Systems: Suitable for 10kV neutral ungrounded systems, arc suppression coil grounded systems, and low-resistance grounded systems.
Core Functions:
Automatic isolation of single-phase grounding faults: When a single-phase grounding fault occurs on the user side, it can automatically open to isolate the faulty branch, avoiding impact on the power supply of non-fault areas.
Automatic isolation of phase-to-phase short-circuit faults: It opens immediately when a phase-to-phase short circuit occurs on the user side, quickly isolating the faulty line.
Fast fault location: Only the responsible user will have a power outage after operation, and fault information can be reported to help operation and maintenance personnel quickly locate and handle the fault.
User load monitoring: Equipped with communication function, it can upload detection data to the monitoring center to realize remote load monitoring.
Structure Composition: It usually consists of two main parts: the switch body and the measurement and control unit, including external voltage transformers, built-in current transformers, CPU processors, and communication modules, etc.
Fault Handling Logic
Its fault handling methods vary according to the system grounding mode and the location of the fault (inside or outside the user's boundary). The specific logic is as follows:
Single-phase grounding fault:
When it occurs inside the user's boundary, for ungrounded systems or arc suppression coil grounded systems, it will trip after being judged as grounding; for low-resistance grounded systems, it will trip before the substation protection action.
When it occurs outside the user's boundary, the sectionalizer will not operate.
Phase-to-phase short-circuit fault:
When it occurs inside the user's boundary, the sectionalizer will open.
When it occurs outside the user's boundary, it will not operate.
Setting Coordination and Installation and Maintenance Key Points
Protection Setting Configuration: Its operating current and time limit need to coordinate with the substation outgoing line protection settings to ensure selectivity. For example, in a neutral ungrounded system, the single-phase grounding action time limit usually needs to avoid instantaneous grounding and be later than the substation grounding signal, and 6 to 8 seconds can be selected; in a low-resistance grounded system, it needs to coordinate with the substation zero-sequence protection.
Installation Notes:
It can only be installed on branch lines or ends, and shall not be used in series.
It is usually installed on the pole of the 10kV overhead distribution line branch as the demarcation point with the user.
According to whether the user's service line is overhead or cable, there are corresponding specific requirements for the wiring method.
Operation and Maintenance Requirements:
Regular inspection of appearance, status, connectors, insulators, lightning arresters, and grounding devices, etc., is required.
The controller's fault indicator light will continue to flash for 48 hours after operation, and a report should be made in time.
The cleaning and inspection cycle is the same as the line pole-climbing inspection, and replacement and maintenance should be considered after more than 10 years of operation.
Application Background and Value
The structure of 10kV feeder overhead lines is complex, with high failure rates, and traditional protection methods are prone to cause power outages of the whole line due to end faults. The application of FZW28 sectionalizer can effectively isolate fault areas, reduce the scope of power outages, and speed up fault recovery. It is one of the key equipment to improve the power supply reliability of distribution networks, especially multi-branch overhead lines.