JTY-GM-HA221-RS485 Network-Type Smoke and Temperature Fire Detector (hereinafter referred to as the "detector") is suitable for fire pre-alarming in civil and industrial places such as box-type substations, cabinets, substations, warehouses, and motor rooms. The detector features high sensitivity, stability and reliability, low power consumption, beautiful and durable appearance, and easy operation, and can be used in conjunction with security systems.
I. Performance:
Alarm sound: ≥80dB
Power supply: DC9V~DC28V
Current: Quiescent current ≤200uA; Alarm current ≤45mA
Operating temperature: -40℃~+80℃; Alarm temperature: 57-60℃
Relative humidity: ≤95%RH (40℃±2℃)
Smoke sensitivity: 1.06±0.26%FT
Compliant standard: GB4715-2005
Communication interface: RS-485; Communication protocol: Modbus-RTU
II. Functions:
Self-test: Press the test button, the detector's LED stays on continuously and emits an alarm sound at the same time. (Note: The self-test only checks the internal functions of the detector itself, and no relay signal is output during the self-test.)
Operation: Under normal circumstances, the detector's indicator light flashes approximately every 6 seconds. The detector automatically detects the smoke concentration in the surrounding environment and performs automatic sensitivity compensation according to the usage environment. When the smoke concentration approaches the alarm value, the detector accelerates the intelligent calculation of the smoke concentration trend, and the alarm indicator light starts flashing. If the calculation result reaches or exceeds the alarm value, the detector starts audible and visual alarm. When the smoke concentration in the surrounding environment drops below the alarm value, the detector automatically returns to normal working status. When the on-site temperature of the detector reaches 57℃, the detector's indicator light starts flashing; when the on-site temperature drops below 57℃, the detector automatically returns to normal working status.
RS-485 Communication: Adopts a standard RS-485 communication interface, and the communication baud rate can be selected as: 2400bps, 4800bps, 9600bps, 19200bps, with the default being 4800bps. Modbus-RTU Protocol: The alarm status register address is 03, which is read using function code 03. The status is "0" or "1": normally open ("1" is normal, "0" is alarm); normally closed ("0" is normal, "1" is alarm).
All products have complete certifications, welcome to inquire. www.szhsj119.com
Shenzhen Hongsheng High-Tech Electronics Co., Ltd.
Contact person: Mr. Chen Cheng
Phone: 【15889370119】 (WeChat same number)
| Industry Category | Electronic Components & Supplies/Sensors/Displacement Sensors |
|---|---|
| Product Category | |
| Brand: | 宏盛佳 |
| Spec: | JTY-GM-HA221-RS485 |
| Stock: | 1000000 |
| Manufacturer: | 深圳市宏盛高科电子有限公司 |
| Origin: | 114403 |