Dry Pendent Sprinkler
Contact Info
- Add:福建省晋江市池店镇华洲小区5幢商铺1408号, Zip: 362200
- Contact: 叶经理
- Tel:15060905319
- Email:79592167@qq.com
Other Products
1. Description of Dry Pendent Sprinklers
Dry sprinklers are designed with stainless steel internal components and are primarily used in dry or pre-action systems, as well as in situations where sprinklers or partial sprinkler connections are exposed to freezing environments, or where seasonal shutdown requires draining the fire sprinkler system piping network to prevent freezing. These sprinklers can also be used in wet sprinkler systems in areas prone to freezing.
Product Standard: GB5135.1 "Automatic Sprinkler Systems - Part 1: Sprinklers"
Design Code: GB50084 "Code for Design of Automatic Sprinkler Systems"
Acceptance Code: GB50261 "Code for Installation and Acceptance of Automatic Sprinkler Systems"
2. Features of Dry Pendent Sprinklers
Dry sprinklers consist of a frame assembly, glass bulb, seals, internal and external decorative plates, external connecting pipe, and sealing seat ring. Under normal conditions, the dry sprinkler remains in a closed state, with the seal at the water inlet preventing water from entering the sprinkler piping. When a fire occurs, the heat-sensitive glass bulb reaches its activation temperature, causing the bulb to break and the base to detach. Simultaneously, the internal mechanism of the dry sprinkler is released, allowing water to flow and activating the sprinkler for fire suppression.
3. Technical Performance of Dry Pendent Sprinklers
(1) Nominal Diameter: φ15mm; Connection Thread: R2 1″
(2) Flow Coefficient: K=80
(3) Rated Working Pressure: 1.2MPa
(4) Installation Type: Pendent
(5) Sensitivity: Φ3mm (Quick Response), Φ5mm (Special Response)
(6) Sprinkler Rated Activation Temperature and Color Code:
Nominal Activation Temperature ℃ | Maximum Ambient Temperature ℃ | Glass Bulb Liquid Color |
68 | 38 | Red |
Model Specification | T-ZSTGX15-68 | K-ZSTGX15-68 |
Flow Coefficient | 80 | |
Glass Bulb Specification | 5MM | 3MM |
Connection Thread | R1” | |
Length | Can be customized according to customer requirements | |
Nominal Activation Temperature | 68°C | |
Application Locations | Dry sprinklers are specifically designed for areas where sprinklers may be exposed to low temperatures and freezing conditions, such as unheated warehouses, freezing environments, and outdoor platforms. | |
| Industry Category | Security-Protection |
|---|---|
| Product Category | |
| Brand: | 泰科TYCO |
| Spec: | 干式下垂型喷头 |
| Stock: | |
| Origin: | China / Fujian / Quanzhoushi |