NR-610 Microcomputer Protection Device
Contact Info
- Add:宜昌市西陵区港城路6号, Zip: 443100
- Contact: 蒋应娟
- Tel:18062398092
- Email:3052844599@qq.com
Other Products
Nanhong Electric NR-610 Microcomputer Protection Device
I Overview
1.1 Scope of Application
The NR-610 microcomputer protection device is suitable for small current grounding systems with voltage levels of 66kV and below. Based on a universal design concept with reasonable functional configuration, this product can be used for general protection of incoming lines, outgoing lines, plant transformers, motors, and capacitors.
II. Technical Parameters
2.1 Operating Environmental Conditions
Ambient temperature: -10 to +55°C
Relative humidity: Not exceeding 95%, no condensation
Atmospheric pressure: 80 to 110 kPa
Other conditions: The air around the device should not contain acidic, alkaline, corrosive, or explosive substances, and should have lightning, rain, and snow protection facilities.
Standard atmospheric conditions for testing:
Ambient temperature: +15 to +35°C
Relative humidity: 45% to 75%
Atmospheric pressure: 86 to 106 kPa
Storage and transportation: -25 to +70°C
2.2 Rated Electrical Parameters
Operating power supply: ADC 100 to 264V
Rated current: 5A
Frequency: 50Hz
2.3 Main Technical Specifications
2.3.1 Setting Range and Error:
Current protection setting range: 0.5~50A, error not exceeding ±3% or 0.05A
Setting step: 0.01A
Zero-sequence current setting range: 0.1~5A, error not exceeding ±3% or 0.02A
Setting step: 0.01A
Voltage setting range: 5~150V, error not exceeding ±3%
Setting step: 0.01V
Time setting range: 0.1~99.99s, error not exceeding ±1% or 35ms
Setting step: 0.01s
Inverse time constant setting range: 0.02-1.2
Time delay error not exceeding ±3% or 100ms
2.3.2 Current quick-break trip operation time: Not exceeding 35ms (at 1.5 times operating current)
Non-electrical protection trip operation time: Not exceeding 35ms
2.3.3 Device Power Consumption:
AC current circuit: Not exceeding 1VA/phase
AC voltage circuit: Not exceeding 1VA/phase
DC voltage circuit: During normal operation, not exceeding 10W
During protection operation, not exceeding 15W
2.3.4 Overload Capacity:
Current circuit: Can operate continuously at 2 times rated current
10 times rated current allowed for 10 seconds
20 times rated current allowed for 1 second
Voltage circuit: Can operate continuously at 1.2 times rated voltage
1.5 times rated voltage allowed for 10 seconds
| Industry Category | Electrical-Equipment-Supplies |
|---|---|
| Product Category | |
| Brand: | 南宏电力 |
| Spec: | NR-610 |
| Stock: | 100 |
| Manufacturer: | |
| Origin: | China / Hubei / Yichangshi |