CSC-237A Digital Motor Comprehensive Protection and Control Device
Contact Info
- Add:宜昌市西陵区港城路6号, Zip: 443100
- Contact: 蒋应娟
- Tel:18062398092
- Email:3052844599@qq.com
Other Products
Beijing Sifang CSC-237A Digital Motor Comprehensive Protection and Control Device
1 Device Introduction
This device is suitable for various non-directly grounded neutral systems of 10kV and below, serving as comprehensive protection for phase-to-phase faults, overload, locked rotor, etc., in large and medium-sized asynchronous motors (hundreds of kilowatts and above). It can be installed locally in switchgear cabinets.
10.2 Main Functions
10.2.1 Protection Functions
Instantaneous overcurrent protection for phase-to-phase faults (optional phase directional element blocking)
Overcurrent protection for locked rotor conditions
Overload protection (optional trip or alarm only)
Long start protection
Overheating protection (overheat trip, overheat alarm, thermal accumulation memory function)
Unbalance protection (phase loss/reverse phase, negative sequence overcurrent protection, optional definite time or inverse time)
Ground fault protection (zero-sequence overcurrent protection, optional trip or alarm only)
Undervoltage protection
F-C overcurrent blocking
Non-electrical protection
10.2.2 Measurement and Control Functions
15 channels of digital input for remote signaling collection, device remote signaling status change, accident remote signaling
Normal circuit breaker remote control opening and closing
Remote measurement of analog quantities such as Ua, Ub, Uc, Ia, Ic, P, Q, COSф
Various event SOE, etc.
4-20mA function
10.3 Protection Elements
10.3.1 Long Start Protection
The method for the device to measure the motor starting time Tstart: timing begins when the maximum phase current of the motor suddenly changes from zero to 10%Ie, and ends when the starting current peaks and drops to 120%Ie. The duration between these points is called Tstart. (Ie is the motor rated current.) Excessive motor starting time can cause rotor overheating. When the actual measured starting time by the device exceeds the set allowable starting time Tstart, the protection acts to trip. The long start protection can be enabled or disabled by the control word "Motor Start Discrimination".