PDM-803DL-C+E-20A-400V Three-Phase Rail-Mounted Energy Meter
Contact Info
- Add:宜昌市西陵区港城路6号, Zip: 443100
- Contact: 蒋应娟
- Tel:18062398092
- Email:3052844599@qq.com
Other Products
Dandong Huatong PDM-803DL-C+E-20A-400V Three-Phase Rail-Mounted Energy Meter
Technical Specifications
Input Current
· Rated Current: 1A, 5A
· Input Load: Maximum 0.1VA
Input Voltage
· Rated Voltage: AC100V, 400V, 57.5/100V, 220/380V
· Input Load: Maximum 0.1VA
Operating Parameters
· Device Power Supply: AC/DC 85V~265V Universal
or AC220V±20%
· Device Power Consumption: <3W
· Operating Temperature: -20℃~60℃
· Storage Temperature: -40℃~80℃
· Relative Humidity: 20%~95% Non-Condensing
Dimensions (L×W×H)
· 9-Square Short Size: 96 mm×96 mm×80 mm
· 9-Square Long Size: 96 mm×96 mm×120 mm
· 9-Square Mounting Hole Size: 92 mm×92 mm
· 42-Square Outer Dimensions: 120 mm×120 mm×120 mm
· 42-Square Mounting Hole Size: 112 mm×112 mm
Installation Measurement
· Data Update Cycle: 450ms
· PT Setting Range: 1.000~9999
· Voltage Accuracy: 0.2% (Full Scale Value)
· Current Measurement Range: 20mA~6A
· CT Setting Range: 1.000~9999
· Current Accuracy: 0.2% (Full Scale Value)
· Single-Phase Power: -9999~9999W/var/VA Excluding CT/PT
· Combined Phase Power: -9999~9999W/var/VA Excluding CT/PT
· Frequency Measurement Range: 45Hz~75Hz
· Power Factor: 0~+1.000
· Other Accuracy: 0.5%
Insulation Strength
· Insulation Resistance: ≥500MΩ
· Voltage Input Terminal: 2.0kV
· Current Input Terminal: 2.0kV
· Remote Signal Input Terminal: 2.0kV
· Power Input Terminal: 2.0kV
Electromagnetic Compatibility
· Surge Immunity: Power 4.0kV Signal Line 2.0kV
· Fast Transient Burst: Power 4.0kV Signal Line 2.0kV5kHz
· Electrostatic Discharge: Contact Discharge 6.0kV Air Gap Discharge 8.0kV
· Radiated RF Field: 10V/m
| Industry Category | Electrical-Equipment-Supplies |
|---|---|
| Product Category | |
| Brand: | 丹东华通 |
| Spec: | PDM-803DL-C+E-20A-400V |
| Stock: | 1 |
| Manufacturer: | |
| Origin: | China / Hubei / Yichangshi |